Subscribe

ADJACENCIES · July 4, 2026

Insulation R-Value Chart: By Material, Zone, and Thickness

Insulation R-value chart: R-per-inch by material, thickness needed for R-30 to R-60, and attic R-value by climate zone. Fiberglass, foam, cellulose compared.

An insulation R-value chart shows how much thermal resistance each material provides per inch and how many inches you need to hit a target R-value. R-value measures resistance to heat flow: higher numbers slow heat loss and heat gain more. Total R-value equals the R-per-inch of the material multiplied by its installed thickness, so a 10-inch layer of fiberglass batt at R-3.2 per inch delivers about R-32.

The chart below is the fast reference. It leads with R-value per inch by material, then the thickness needed to reach the common attic targets, then the 2021 IECC climate-zone recommendations that decide which target applies to your roof and attic.

Insulation R-value chart per inch by material

R-value per inch is the single number that lets you compare materials fairly. Rigid foams and closed-cell spray foam pack the most resistance into the least thickness, which matters where roof or cavity depth is limited. Fiberglass and cellulose cost less per R but need more depth. The ranges below reflect published manufacturer and Department of Energy figures at standard 75 degree F test conditions.

Material R-value per inch Common use
Closed-cell spray foam R-6.0 to R-7.0 Roof decks, cathedral ceilings, tight cavities
Polyisocyanurate (polyiso) board R-5.6 to R-6.5 Low-slope commercial roofs, continuous exterior
XPS rigid foam board R-4.5 to R-5.0 Below grade, continuous exterior sheathing
EPS rigid foam board R-3.6 to R-4.4 Continuous exterior, roof cover board
Mineral wool (rockwool) batt R-3.8 to R-4.3 Walls, fire-rated assemblies, sound control
High-density fiberglass batt R-3.7 to R-4.3 2×4 and 2×6 walls at higher R
Open-cell spray foam R-3.5 to R-3.8 Roof decks, interior walls, sound control
Dense-pack cellulose R-3.5 to R-3.8 Enclosed walls, dense-pack cavities
Loose-fill cellulose R-3.2 to R-3.8 Attic floors, blown application
Standard fiberglass batt R-3.0 to R-3.7 Walls, floors, standard batts
Blown-in (loose-fill) fiberglass R-2.2 to R-2.7 Attic floors over drywall

Two numbers stand out for roofers and homeowners. Closed-cell spray foam roughly doubles the R-per-inch of loose-fill fiberglass, so it hits code in a fraction of the depth. Blown-in fiberglass sits at the bottom of the chart, which is why an attic that looks full at 10 inches may still fall short of R-30.

Fiberglass insulation R-value chart

Fiberglass R-value depends on form and density. Standard batts run R-3.0 to R-3.7 per inch, high-density batts reach R-3.7 to R-4.3, and blown-in (loose-fill) fiberglass settles at R-2.2 to R-2.7 per inch. That spread is why the same brand can label one product R-13 and another R-15 at the same nominal thickness. The batt table below gives the standard nominal R-values sold at retail.

Fiberglass batt R-value Nominal thickness Typical framing
R-11 3.5 in 2×4 wall (low density)
R-13 3.5 in 2×4 wall (standard)
R-15 3.5 in 2×4 wall (high density)
R-19 6.25 in 2×6 wall, floors
R-21 5.5 in 2×6 wall (high density)
R-30 9.5 in Attic, cathedral ceiling
R-38 12 in Attic floor
R-49 15.5 in Cold-climate attic

Note the R-19 to R-21 detail: an R-19 batt is designed for a 6.25-inch cavity, so compressing it into a 5.5-inch 2×6 wall drops its real performance. A purpose-made R-21 high-density batt fills that same 5.5-inch cavity without compression, which is why builders spec R-21 for 2×6 walls.

How thick does insulation need to be for each R-value?

Insulation thickness by R-value is found by dividing the target R-value by the material’s R-per-inch. To reach R-49 in an attic you need about 15 inches of fiberglass batt, 13.5 inches of cellulose, or 8 inches of closed-cell spray foam. The table maps the four common attic targets to each material so you can size a job or sanity-check a quote.

Target R-value Blown fiberglass Fiberglass batt Loose-fill cellulose Open-cell spray foam Closed-cell spray foam
R-30 12 to 13 in 9.5 in 8 to 9 in 8 to 8.5 in 4.5 to 5 in
R-38 15 to 16 in 12 in 10.5 to 11 in 10 to 11 in 5.5 to 6.5 in
R-49 19 to 20 in 15.5 in 13.5 to 14 in 13 to 14 in 7 to 8 in
R-60 23 to 25 in 19 in 16.5 to 17 in 16 to 17 in 8.5 to 10 in

Depth matters on a roof where headroom or rafter depth is fixed. A 2×10 rafter gives about 9.25 inches of cavity. Filling it with open-cell foam reaches roughly R-33, while closed-cell foam in the same depth can hit R-55 or more, which is often the only way to meet a cold-climate ceiling target without furring down the rafters.

Ceiling and attic insulation R-value by climate zone

The 2021 International Energy Conservation Code (IECC) sets minimum ceiling and attic R-values by climate zone, and most jurisdictions adopt it or a close version. Attic requirements run from R-30 in the warmest zone to R-60 in the coldest. The Department of Energy recommendations track closely. Find your zone on the IECC climate map, then read across.

Climate zone Example regions Attic / ceiling R-value Wood-frame wall Floor
Zone 1 South Florida, Hawaii R-30 R-13 to R-15 R-13
Zone 2 Gulf Coast, Phoenix R-49 R-13 to R-15 R-13
Zone 3 Atlanta, Los Angeles R-49 R-20 or R-13+5 R-19
Zone 4 Virginia, Kansas R-60 R-30 or R-20+5 R-19
Zone 5 Chicago, Denver R-60 R-30 or R-20+5 R-30
Zone 6 Minneapolis, Vermont R-60 R-30 or R-20+5 R-30
Zone 7 Northern Minnesota R-60 R-30 or R-20+5 R-38
Zone 8 Interior Alaska R-60 R-30 or R-20+5 R-38

The jump from Zone 1 to Zone 2 is the one people miss: it goes straight from R-30 to R-49, skipping R-38. So a builder in the Gulf Coast who tops out at R-38 is a full step below current code. Zones 4 through 8 all share the R-60 ceiling target under the 2021 IECC, which is a notable increase from the older R-49 many older homes carry.

How to read the chart for a real roof or attic job

To use the chart, find your climate zone first, read the attic target, then pick a material and the thickness that hits it. Zone decides the number; material and available depth decide how you get there. Existing insulation counts toward the total, so measure what is already in the attic before you add.

  1. Locate your climate zone on the IECC map and read the attic/ceiling R-value from the zone table above.
  2. Measure existing insulation depth and multiply by that material’s R-per-inch to get the R-value already in place.
  3. Subtract the existing R-value from your target to find the R-value still needed.
  4. Pick a material and use the thickness table to convert the remaining R-value into inches to install.
  5. Check clearances for soffit vents, recessed lights (IC-rated only for direct contact), and rafter depth before you commit to a depth.

One field caution: R-value assumes the insulation is dry, uncompressed, and installed without gaps. Compressed batts, wind-washed loose-fill near eaves, and missing air sealing all cut real-world performance below the labeled number. For roof and attic assemblies, pairing the right R-value with proper attic ventilation keeps moisture from degrading the insulation and the deck above it.

Rigid foam and continuous insulation R-value

Rigid foam boards carry the highest R-per-inch among common products and are used as continuous insulation over sheathing or roof decks, where they also cut thermal bridging through framing. Polyiso leads at R-5.6 to R-6.5 per inch, XPS follows at R-4.5 to R-5.0, and EPS runs R-3.6 to R-4.4. A “+5” in a wall code line, such as R-20+5, means R-20 in the cavity plus R-5 of continuous foam on the exterior.

Rigid foam R-value per inch R-value at 2 in Notes
Polyiso R-5.6 to R-6.5 R-11 to R-13 R drops in cold; verify aged R-value
XPS R-4.5 to R-5.0 R-9 to R-10 Moisture resistant, below grade
EPS R-3.6 to R-4.4 R-8 to R-9 Lowest cost per R, drainable

Polyiso carries one caveat the label rarely shows: its R-value can fall in cold temperatures, so some designers derate it in Zone 6 and above. On low-slope commercial roofs, polyiso is still the dominant board because of its high R-per-inch and code acceptance, a pattern covered in our roofing material carbon report.

FAQ

What R-value do I need for my attic?

Attic R-value depends on your climate zone under the 2021 IECC. Zone 1 needs R-30, Zones 2 and 3 need R-49, and Zones 4 through 8 need R-60. The Department of Energy recommends R-49 to R-60 for most homes in cold climates and R-30 to R-49 in warm ones. Check your local code, since some jurisdictions still enforce older R-49 minimums.

What is the R-value of fiberglass insulation per inch?

Fiberglass R-value ranges from R-2.2 to R-2.7 per inch for blown-in loose-fill, R-3.0 to R-3.7 for standard batts, and R-3.7 to R-4.3 for high-density batts. Loose-fill sits lowest because it is fluffier and less dense. To estimate total R-value, multiply the R-per-inch by the installed depth measured in the attic.

How many inches of insulation do I need for R-49?

Reaching R-49 takes about 19 to 20 inches of blown-in fiberglass, 15.5 inches of fiberglass batt, 13.5 to 14 inches of loose-fill cellulose, or 7 to 8 inches of closed-cell spray foam. Denser and higher R-per-inch materials need less depth, which matters when rafter or joist depth is limited.

Which insulation has the highest R-value per inch?

Closed-cell spray foam has the highest R-value per inch of common insulations at R-6.0 to R-7.0, followed by polyisocyanurate rigid board at R-5.6 to R-6.5. These materials hit code targets in the least thickness, which makes them the usual choice for shallow roof decks, cathedral ceilings, and continuous exterior insulation.

Does more R-value always mean better performance?

Not always. R-value only measures conductive heat resistance in a dry, uncompressed, gap-free layer. Air leaks, missing air sealing, compressed batts, and moisture can each cut real performance well below the labeled R-value. In practice, air sealing plus a code-level R-value often outperforms a higher R-value installed poorly, and roof assemblies also need adequate ventilation to stay dry.

How is total R-value calculated?

Total R-value equals the material’s R-per-inch multiplied by its installed thickness. For example, 12 inches of loose-fill cellulose at R-3.5 per inch gives about R-42. When layers stack, such as batt plus continuous foam board, you add each layer’s R-value together to get the assembly total, which is how “+5” wall code lines work.

Related reading: our full attic insulation guide covers types and cost by zone, blown-in insulation breaks down loose-fill cost and DIY versus pro, and the best insulation for an attic helps you match material to your situation.

Reviewed by The Roofing Brief Team. Last reviewed July 2026.